PGS-L Series Cable Type SF6 Insulated Pole-mounted Load Break Switch - Liyond
Home/Outdoor High-Voltage Switchgear/Outdoor Load Break Switch/PGS-L Series Cable Type SF6 Insulated Pole-mounted Load Break Switch

PGS-L Series Cable Type SF6 Insulated Pole-mounted Load Break Switch

The PGS-L series is engineered for high-humidity, high-salinity coastal regions and narrow installation spaces. By replacing exposed terminal lugs with molded cable outlets or split rubber bushings, the system achieves a fully insulated and fully sealed (SIS) configuration, preventing phase-to-phase flashovers caused by external environments.

Electrical ProductsElectrical Products

Product Features of Cable Type SF6 Insulated Pole-mounted Load Break Switch

Fully Insulated Design: All conductive parts are enclosed, allowing for reduced phase-to-phase clearance and installation on compact single-pole cross-arms.

Bushing Protection Protocol: The enclosure features a “Forbid Lifting Bushing” warning and specialized lifting lugs to protect the hermetic seal from mechanical stress during installation.

Self-Powered Spring Mechanism: Independent spring actuation ensures switching speeds are consistent regardless of operator force, ensuring rapid arc quenching.

High Environmental Durability: Specifically suited for Class IV pollution levels and areas prone to wildlife-induced faults.

Technical Parameters of Cable Type SF6 Insulated Pole-mounted Load Break Switch

No. Name Unit Data
Product mode PGS-12 PGS-24 PGS-40.5
1 Rated voltage kV 12 24 40.5
6/10/11 15/17.5/20 33/36/40.5
2 Rated frequency Hz 50/60 50/60 50/60
3 Rated insulation level (SF6 filled at 0.07MPa / 20°C) Lightning impulse withstand voltage phase to phase, phase to ground kV 75 125 170(185)
Fracture 85 145 180(215)
Power frequency withstand voltage 1min phase to phase, phase to ground kV 45 50(64) 70(95)
Fracture 50 60(79) 95(110)
4 Insulation level at zero gauge pressure Power frequency withstand voltage 1min kV 30
Reverse phase withstand voltage 1min 30
Highest phase voltage 5min 9
5 Rated current A 630(400) 630(400) 630(400)
6 Rated breaking load current (at 0.07MPa / 20°C) A 630(400) 630(400) 630(400)
7 Breaking current under zero gauge pressure A 630(400) 630(400) 630(400)
8 Peak withstand current kA 50 50 50
9 Rated short-time making current kA 50 50 50
11 Rated short-time withstand current KA/s 20/4 20/4 20/4
12 Rated cable charging breaking current A 25 25 25
13 Rated line charging breaking current A 16 16 16
14 Rated closed-loop breaking current A 630(400) 630(400) 630(400)
15 Exciting current A 21 21 21
16 Rated current breaking times Times ≥400 ≥400 ≥400
17 Rated working pressure MPa 0.07 0.07 0.25
18 Per-phase main circuit resistance μΩ ≤150 ≤150 ≤150
19 Relative gas leakage rate year ≤1% ≤1% ≤1%
20 SF6 gas moisture content Factory transfer value ppm ≤150 ≤150 ≤150
Switch operating value ppm ≤300 ≤300 ≤300
21 Mechanical stability operations times 6000 6000 6000
22 Rated operating voltage and auxiliary circuit rated voltage V DC 220/110/48/24 DC 220/110/48/24 DC 220/110/48/24
AC 220/110 AC 220/110 AC 220/110
23 Weight Type M kg 115 125 135
Type A 135 145 155
24 Enclosure protection rating of mechanism box and controller IP44  IP54
25 Type of mounting Lifting type (suspended)/seat type (horizontal)

Applications
Coastal power lines, industrial zones with heavy pollution, and distribution nodes connecting overhead lines to underground cables.

Ordering Information of Cable Type SF6 Insulated Pole-mounted Load Break Switch

To ensure the technical compatibility and accurate configuration of your PGS Series SF6 Load Break Switch, please specify the following details in your inquiry or purchase order:

No. Item Technical Requirements & Specifications
1 Product Model □ PGS-12    □ PGS-24    □ PGS-40.5
2 Rated Voltage □ 12kV        □ 24kV        □ 40.5kV
3 Rated Current □ 630A (Standard)    □ Other: ________
4 Operation Type □ Manual (Hook-stick)    □ Motorized (Remote)    □ Automatic (FTU)
5 Control Voltage □ AC 220V    □ DC 24V    □ DC 48V    □ N/A (Manual)
6 Outlet Interface □ Terminal Outlet (Standard)    □ Cable Outlet (L-Type)
7 Bushing Material □ Silicone Rubber (Organic)    □ Porcelain (Ceramic)
8 Integrated Add-ons □ Arrester (B-Type)    □ Busbar Fixtures    □ None
9 Mounting Bracket □ Seating Type (Base)    □ Hanging Type (Suspension)
10 Service Condition Altitude: ________ m    Ambient Temp: ________ ℃
11 Quantity ________ Units

Get in Touch with Liyond

We're here to help! Connect with our team for expert support and personalized solutions.

Power your projects with long-lasting switchgear and switchgear components from Liyond.

We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.          Privacy Policy
Reject Accept
error: Content is protected !!