The PGS series is an SF6 gas-insulated sectionalizer designed for medium-voltage overhead distribution lines. The switch is hermetically sealed within a 3.0mm grade 304 stainless steel enclosure, filled with SF6 gas at a rated pressure of 0.05 MPa. It provides simultaneous three-phase operation with high breaking capacity for load currents and short-circuit making capacity.
Integrated Polymeric Bushings: Molded silicone rubber bushings provide a creepage distance of over 25mm/kV, ensuring high resistance to pollution and UV radiation.
Flat Terminal Connection: Standardized copper terminal lugs allow for direct bolt-on connection with overhead conductors or jumpers.
Mechanical Interlock & Indicator: Features a high-visibility mechanical ON/OFF indicator and a manual locking device to prevent unauthorized or accidental operation.
Maintenance-Free Sealing: Automated robotic welding ensures an annual leakage rate of ≤0.1%, eliminating the need for gas refilling throughout its 20-year service life.
| No. | Name | Unit | Data | |||||
| Product mode | PGS-12 | PGS-24 | PGS-40.5 | |||||
| 1 | Rated voltage | kV | 12 | 24 | 40.5 | |||
| 6/10/11 | 15/17.5/20 | 33/36/40.5 | ||||||
| 2 | Rated frequency | Hz | 50/60 | 50/60 | 50/60 | |||
| 3 | Rated insulation level (SF6 filled at 0.07MPa / 20°C) | Lightning impulse withstand voltage | phase to phase, phase to ground | kV | 75 | 125 | 170(185) | |
| Fracture | 85 | 145 | 180(215) | |||||
| Power frequency withstand voltage 1min | phase to phase, phase to ground | kV | 45 | 50(64) | 70(95) | |||
| Fracture | 50 | 60(79) | 95(110) | |||||
| 4 | Insulation level at zero gauge pressure | Power frequency withstand voltage 1min | kV | 30 | ||||
| Reverse phase withstand voltage 1min | 30 | |||||||
| Highest phase voltage 5min | 9 | |||||||
| 5 | Rated current | A | 630(400) | 630(400) | 630(400) | |||
| 6 | Rated breaking load current (at 0.07MPa / 20°C) | A | 630(400) | 630(400) | 630(400) | |||
| 7 | Breaking current under zero gauge pressure | A | 630(400) | 630(400) | 630(400) | |||
| 8 | Peak withstand current | kA | 50 | 50 | 50 | |||
| 9 | Rated short-time making current | kA | 50 | 50 | 50 | |||
| 11 | Rated short-time withstand current | KA/s | 20/4 | 20/4 | 20/4 | |||
| 12 | Rated cable charging breaking current | A | 25 | 25 | 25 | |||
| 13 | Rated line charging breaking current | A | 16 | 16 | 16 | |||
| 14 | Rated closed-loop breaking current | A | 630(400) | 630(400) | 630(400) | |||
| 15 | Exciting current | A | 21 | 21 | 21 | |||
| 16 | Rated current breaking times | Times | ≥400 | ≥400 | ≥400 | |||
| 17 | Rated working pressure | MPa | 0.07 | 0.07 | 0.25 | |||
| 18 | Per-phase main circuit resistance | μΩ | ≤150 | ≤150 | ≤150 | |||
| 19 | Relative gas leakage rate | year | ≤1% | ≤1% | ≤1% | |||
| 20 | SF6 gas moisture content | Factory transfer value | ppm | ≤150 | ≤150 | ≤150 | ||
| Switch operating value | ppm | ≤300 | ≤300 | ≤300 | ||||
| 21 | Mechanical stability operations | times | 6000 | 6000 | 6000 | |||
| 22 | Rated operating voltage and auxiliary circuit rated voltage | V | DC 220/110/48/24 | DC 220/110/48/24 | DC 220/110/48/24 | |||
| AC 220/110 | AC 220/110 | AC 220/110 | ||||||
| 23 | Weight | Type M | kg | 115 | 125 | 135 | ||
| Type A | 135 | 145 | 155 | |||||
| 24 | Enclosure protection rating of mechanism box and controller | IP44 IP54 | ||||||
| 25 | Type of mounting | Lifting type (suspended)/seat type (horizontal) | ||||||
Applications
Mainline sectionalizing and branch isolation for 12kV-40.5kV overhead distribution networks, and feeder automation projects.
To ensure the technical compatibility and accurate configuration of your PGS Series SF6 Load Break Switch, please specify the following details in your inquiry or purchase order:
| No. | Item | Technical Requirements & Specifications |
| 1 | Product Model | □ PGS-12 □ PGS-24 □ PGS-40.5 |
| 2 | Rated Voltage | □ 12kV □ 24kV □ 40.5kV |
| 3 | Rated Current | □ 630A (Standard) □ Other: ________ |
| 4 | Operation Type | □ Manual (Hook-stick) □ Motorized (Remote) □ Automatic (FTU) |
| 5 | Control Voltage | □ AC 220V □ DC 24V □ DC 48V □ N/A (Manual) |
| 6 | Outlet Interface | □ Terminal Outlet (Standard) □ Cable Outlet (L-Type) |
| 7 | Bushing Material | □ Silicone Rubber (Organic) □ Porcelain (Ceramic) |
| 8 | Integrated Add-ons | □ Arrester (B-Type) □ Busbar Fixtures □ None |
| 9 | Mounting Bracket | □ Seating Type (Base) □ Hanging Type (Suspension) |
| 10 | Service Condition | Altitude: ________ m Ambient Temp: ________ ℃ |
| 11 | Quantity | ________ Units |
We're here to help! Connect with our team for expert support and personalized solutions.
Check out these related products you might also be interested in.
Get A QuotePower your projects with long-lasting switchgear and switchgear components from Liyond.