This VSG spring operating mechanism is for VSG-40.5 vacuum circuit breaker, is a type of front indoor high voltage VCB, suitable for 3 phase AC, 50 Hz, and rated voltage of 40.5kV, and applied in places with breaking of different load and frequent operations as protection and control unit, such as industrial and mining enterprise, power plants and transformer substations.
1. Altitude not exceeding 2000m;
2. Ambient temperature: -15°c ~+40°c;
3. Relative humidity: monthly average not exceeding 95%, daily relative humidity not exceeding 95%;
4. Earthquake level not exceeding 8 class;
5. Without peril of fire, corrosion gas, explosion, vibration.
Item | Unit | Data | |
Rated voltage | kV | 40.5 | |
Rated insulation voltage | 1 min power frequency withstand voltage | kV | 95 |
Lightning impulse withstand voltage(peak) | kV | 185 | |
Rated frequency | Hz | 50 | |
Rated current | A | 1250,1600,2000,2500,3150 | |
Rated short-time withstand current | kV | 25,31.5 | |
Rate peak withstand current | 63,80 | ||
Rate short-circuit duration | S | 4 | |
a.c. component of rate short-circuit breaking current | kA | 42 | |
Rated short-circuit making current | kA | 63,80,100 | |
Mechanical life | time | 10000 | |
Permitted abrasion thickness of moving and fixed contacts | mm | 3 | |
Arcing time | ms | ≤15 |