FN18 load switches and load switch-fuse combinations are high-voltage, high-performance load switches combining compressed-air arc extinguishing and gas-produced arc extinguishing.
The combination of load switch and fuse combines the advantages of the load switch with those of the fuse to switch any load current up to the rated breaking current of the load switch, and to switch any overcurrent up to the rated short-circuit breaking current of the combination by means of the operation of the fuse and its impinger.
1. Ambient temperature:
Maximum +40°C Maximum 24 hour average +35°C
Minimum (according to “minus 5 indoorclass” )-15°C.
2. Humidity:
Daily average ambient air relative humidity≤95%, on average≤90%;
Saturated vapor pressure of daily mean values s 2.2 X 10-3Mpa, on averages 1.8 x10- 3Mpa;
Maximum site altitude:s 1000 M above sea level
| Rated voltage | Unit | 12kV | 17.5kV | 24kV | 36kV | 40.5kV | |||||||||||
| Rated current | A | 400 | 630 | 1250 | 400 | 630 | 1250 | 400 | 630 | 1250 | 630 | 800 | 1000 | 630 | 800 | 1000 | |
| Max.rated current | A | 400 | 630 | 1250 | 400 | 630 | 1250 | 400 | 630 | 1250 | 630 | 800 | 800 | 630 | 800 | 800 | |
| Short circuit making capacity | KA peak | 67 | 50 | 50 | 50 | 50 | |||||||||||
| Peak withstand current* | KA peak | 82 | 82 | 82 | 66 | 66 | |||||||||||
| Short time current | 1 sec. | KA eff | 31.5
25 20 |
31.5
25 20 |
31.5
25 20 |
31.5
25 |
31.5
25 |
31.5
25 |
25
25 16 |
25
25 16 |
31.5
25 16 |
25 | 25 | 25 | 25 | 25 | 25 |
| 2 sec. | |||||||||||||||||
| 3 sec. | |||||||||||||||||
| Mainly active load breaking capacity
(test duty 1 and, IEC 60265-1( 265)) |
A | 400 | 630 | 1250 | 400 | 630 | 1250 | 400 | 630 | 1250 | 630 | 800 | 630 | 800 | 630 | 800 | |
| Mainly capacitive breaking capacity
(test duty 4, IEC 60265-1 (IEC 265)) |
A | 150 | 45 | 80 | 50 | 50 | |||||||||||
| Mainly inductive breakingcapacity cosφ=0.15 | A | 16 | 16 | 16 | 16 | 16 | |||||||||||
| Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11) | A | 1600 | 1600 | 1600 | 1600 | 900 | 900 | 300* | 300 | 300 | 300 | 300 | 300 | ||||
| Power frequency withstand voltage 50 Hz 1 min.
-to earth and between poles -across isolating distance |
kV | 42
45 |
45
60 |
55
70 |
80
88 |
95
120 |
|||||||||||
| Impulse withstand voltage 1.2/50 μs
– to earth and between poles – across isolating distance |
kV |
75 85 |
95
110 |
125
145 |
170
195 |
190
220 |
|||||||||||
| Pole distance | mm | 150, 170, 210 | 170,210 | 170,235,275 | 360 | 360 | |||||||||||
| Max. operating torque at:
-closing K/A mech. -opening K/A mech. |
Nm | 115-120 Nm K-mech.120 Nm/A-mech. 3Nm |
80-100 Nm K-mech.80-100 Nm |
||||||||||||||
| Operating angle on the shaft | degree | 130 | 120 | ||||||||||||||
| Opening time | ms | 40-60 | 60 | ||||||||||||||