FN18 12kV 3 Phase Gang Operated Air Load Break Switch With Earthing Device And Fuse Switch Nalf  - Liyond
Home/Load Break Switch/12kV Indoor Load Break Switch/FN18 12kV 3 Phase Gang Operated Air Load Break Switch With Earthing Device And Fuse Switch Nalf 

FN18 12kV 3 Phase Gang Operated Air Load Break Switch With Earthing Device And Fuse Switch Nalf 

FN18 load switches and load switch-fuse combinations are high-voltage, high-performance load switches combining compressed-air arc extinguishing and gas-produced arc extinguishing.
The combination of load switch and fuse combines the advantages of the load switch with those of the fuse to switch any load current up to the rated breaking current of the load switch, and to switch any overcurrent up to the rated short-circuit breaking current of the combination by means of the operation of the fuse and its impinger.

Electrical ProductsElectrical Products

Usage environment of FN18 load break switch

1. Ambient temperature:
Maximum +40°C Maximum 24 hour average +35°C
Minimum (according to “minus 5 indoorclass” )-15°C.
2. Humidity:
Daily average ambient air relative humidity≤95%, on average≤90%;
Saturated vapor pressure of daily mean values s 2.2 X 10-3Mpa, on averages 1.8 x10- 3Mpa;
Maximum site altitude:s 1000 M above sea level

FN18 12kV Air Load Break Switch Technical Parameters

Rated voltage Unit 12kV 17.5kV 24kV 36kV 40.5kV
Rated current A 400 630 1250 400 630 1250 400 630 1250 630 800 1000 630 800 1000
Max.rated current A 400 630 1250 400 630 1250 400 630 1250 630 800 800 630 800 800
Short circuit making capacity KA peak 67 50 50 50 50
Peak withstand current* KA peak 82 82 82 66 66
Short time current 1 sec. KA eff 31.5

25

20

31.5

25

20

31.5

25

20

31.5

25

31.5

25

31.5

25

25

25

16

25

25

16

31.5

25 

16

25 25 25 25 25 25
2 sec.
3 sec.
Mainly active load breaking capacity

(test duty 1 and, IEC 60265-1( 265))

A 400 630 1250 400 630 1250 400 630 1250 630 800 630 800 630 800
Mainly capacitive breaking capacity

(test duty 4, IEC 60265-1 (IEC 265))

A 150 45 80 50 50
Mainly inductive breakingcapacity cosφ=0.15 A 16 16 16 16 16
Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11) A 1600 1600   1600 1600   900 900   300* 300 300 300 300 300
Power frequency withstand voltage 50 Hz 1 min.  

-to earth and between poles                                 

-across isolating distance

kV 42

45

45

60

55 

70

80

88

95

120

Impulse withstand voltage 1.2/50 μs

 – to earth and between poles   

– across isolating distance

kV

75

85

95

110

125

145

170

195

190

220

Pole distance mm 150, 170, 210 170,210 170,235,275 360 360
Max. operating torque at:

-closing K/A mech.                                           

-opening K/A mech.

Nm 115-120 Nm
K-mech.120 Nm/A-mech. 3Nm
80-100 Nm
K-mech.80-100 Nm
Operating angle on the shaft degree 130 120
Opening time ms 40-60 60

FN18 Outline Dimension Drawing

FN18 load break switch drawing

FN18 load break switch drawing

FN18 load break switch structure

FN18 lbs structure

Get in Touch with Liyond

We're here to help! Connect with our team for expert support and personalized solutions.

Power your projects with long-lasting switchgear and switchgear components from Liyond.

We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.          Privacy Policy
Reject Accept
error: Content is protected !!