Liyond 36kV/35kV/40.5kV/33kV Vacuum Circuit Breaker Indoor Switchgear VSG Mechanism Side Type
Home/Vacuum Circuit Breaker/40.5kV Vacuum Circuit Breaker/Liyond Indoor 33kV 35kV 36kV 40.5kV VSG Mechanism Side Type M.V. Vacuum Circuit Breaker

Liyond Indoor 33kV 35kV 36kV 40.5kV VSG Mechanism Side Type M.V. Vacuum Circuit Breaker

VSG/C-40.5 Series Side Mounted Vacuum Circuit Breaker is a new type of three phase 50Hz according to the unique design concept and combined with the market demand and development, the rated voltage of indoor switchgear 40.5kV, it can be provided to industrial and mining enterprises, power plant and substation as the control and protection of electrical equipment, and is suitable for frequent operation.

Electrical ProductsElectrical Products

Applying ambient conditions of VSG/C-40.5 Series Side Mounted Vacuum Circuit Breaker

1. Ambient temperature: -10 °C ~ +40 °C (It allows storage and transportation at -30 degrees centigrade);
2. Ambient humidity: the average humidity of a day should be no more than 95%. The average humidity of a month should be no more than 90%
3. Saturated vapor pressure: the average pressure of a day should be no more than 2.2kPa; the average pressure of a month should be no more than 1 .8kPa;
4. Altitude: < 1500m;
5. Earthquake intensity:≤8 degree;
6. The 33kV circuit breaker should be installed in the place without fire, explosion, serious filth, and chemical erosion and violent vibration.

Technical parameters of VSG/C-40.5 Series Side Mounted Vacuum Circuit Breaker

No. Item Unit Data
1 Rated voltage kV 40.5
2 Rated insulation
level
1 min power frequency withstand voltage (RMS) kV 95
Lightning impulse withstand voltage (peak) kV 185
3 Rated frequency Hz 50
4 Rated current A 1250/1600/2000
5 4S rated short-time withstand current kA 25 31.5
6 Rated peak withstand current kA 63 80
7 Rated short circuit breaking current kA 25 31.5
8 Rated short circuit closing current kA 63 80
9 Rated operating sequence O-0.3s-CO- 180s-CO
10 Rated short circuit breaking current breaking times times 20
11 Breaking current of rated capacitor bank A 630
12 Mechanical Life times 20000

After adjusting the circuit breaker, the mechanical characteristic parameters are shown below

No. Item Unit Data
1 Contact opening distance mm 18±1
2 Contact stroke mm 5±1
3 Average closing speed m/s 0.8±0.2
4 Average breaking speed m/s 1.8±0.2
5 Breaking time(rated voltage) ms 20-50
6 Closing time(rated voltage) ms ≤100
7 Contact closing trip time ms/M ≤3
8 Three phase switching off synchronism ms/M ≤2
9 The movable and static contact allow the accumulated thickness of friction mm 3
10 Dominant loop resistance μΩ ≤60

 

Shape and Installation Dimensions of VSG/C-40.5 Side Mounted VCB

VSG-C-40.5 side VCB drawing

Get in Touch with Liyond

We're here to help! Connect with our team for expert support and personalized solutions.

Power your projects with long-lasting switchgear and switchgear components from Liyond.

We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.          Privacy Policy
Reject Accept
error: Content is protected !!