110kV Oil Immersed OCTC Transformer-10/20MVA Power Transformer up to 180MVA | Liyond
Home/Power Transformer/Oil-Immersed Transformer/110kV Oil-Immersed Power Transformer OCTC Double & Three-winding 6.3-180MVA

110kV Oil-Immersed Power Transformer OCTC Double & Three-winding 6.3-180MVA

The Liyond 110kV class power transformer represents the pinnacle of our high-voltage engineering, developed by integrating advanced domestic and international technologies. Designed with a focus on maximum reliability, this series features low loss, low noise, and low partial discharge. These transformers are built to be maintenance-free (no core lifting required) and fully sealed, significantly reducing operational costs while enhancing the economic efficiency and safety of the power grid.

Electrical ProductsElectrical Products

Key Structural Features of 110kV Oil-Immersed Power Transformer

Advanced Iron Core: Constructed with high-permeability silicon steel sheets using a full-oblique, multi-step longitudinal joint stacking method to drastically reduce no-load loss.

Optimized Windings: High-strength electrical design ensures excellent resistance to short-circuit impacts and overvoltages.

Superior Tank Design: The “no-core-lifting”  structure ensures long-term sealing integrity and reduces on-site maintenance requirements.

Customizable Efficiency: Available in S9, S10, S11 types or even lower-loss customized models to meet specific energy-saving goals.

Main Technical Parameters

Two-Winding Off-Circuit Tap Changer – SF11 Series

Rated Power (kVA) HV (kV) LV (kV) Connection No-Load Loss (kW) Load Loss (kW) No-Load Current (%) Impedance (%) Weight (kg)
10,000 110/121 ±2×2.5% 6.3/6.6/10.5/11 YNd11 10.56 50.35 0.72 10.5 18,100
12,500 110/121 ±2×2.5% 6.3/6.6/10.5/11 YNd11 12.48 59.85 0.72 10.5 24,200
16,000 110/121 ±2×2.5% 6.3/6.6/10.5/11 YNd11 15.04 73.15 0.67 10.5 26,000
20,000 110/121 ±2×2.5% 6.3/6.6/10.5/11 YNd11 17.60 88.35 0.67 10.5 29,800
25,000 110/121 ±2×2.5% 6.3/6.6/10.5/11 YNd11 20.80 104.50 0.62 10.5 31,500
31,500 110/121 ±2×2.5% 6.3/6.6/10.5/11 YNd11 24.64 126.35 0.60 10.5 37,800
40,000 110/121 ±2×2.5% 6.3/6.6/10.5/11 YNd11 29.44 148.20 0.56 10.5 43,200
50,000 110/121 ±2×2.5% 6.3/6.6/10.5/11 YNd11 35.20 184.30 0.52 10.5 57,600
63,000 110/121 ±2×2.5% 6.3/6.6/10.5/11 YNd11 41.60 222.30 0.48 10.5 63,900

Two-Winding On-Load Tap Changer – SFZ11 Series

Rated Power (kVA) HV (kV) LV (kV) Connection No-Load Loss (kW) Load Loss (kW) No-Load Current (%) Impedance (%) Weight (kg)
10,000 110/121 ±8×1.25% 6.3 YNd11 11.36 50.35 0.74 10.5 19,300
12,500 110/121 ±8×1.25% 6.3 YNd11 13.44 59.85 0.74 10.5 22,500
16,000 110/121 ±8×1.25% 6.3 YNd11 16.16 73.15 0.69 10.5 27,350
20,000 110/121 ±8×1.25% 6.3 YNd11 19.20 88.35 0.69 10.5 32,300
25,000 110/121 ±8×1.25% 6.3 YNd11 22.72 104.50 0.64 10.5 37,300
31,500 110/121 ±8×1.25% 6.3 YNd11 27.04 126.35 0.64 10.5 45,100
40,000 110/121 ±8×1.25% 6.3 YNd11 32.32 148.20 0.58 10.5 53,150
50,000 110/121 ±8×1.25% 6.3 YNd11 38.24 184.30 0.58 10.5 61,300
63,000 110/121 ±8×1.25% 6.3 YNd11 45.44 222.30 0.52 10.5 72,900

Three-Winding On-Load Tap Changer – SFSZ11 Series

Rated Power (kVA) HV (kV) MV (kV) LV (kV) Connection No-Load Loss (kW) Load Loss (kW) No-Load Current (%) Impedance (%) Weight (kg)
10,000 110/121 ±8×1.25% 35 6.3 YNyn0d11 13.68 62.70 0.89 HV-MV 17.5–18.5
HV-LV 10.5
MV-LV 6.5
25,700
12,500 110/121 ±8×1.25% 35 6.3 YNyn0d11 16.16 74.10 0.89 HV-MV 17.5–18.5
HV-LV 10.5
MV-LV 6.5
30,700
16,000 110/121 ±8×1.25% 35 6.3 YNyn0d11 19.36 90.25 0.84 HV-MV 17.5–18.5
HV-LV 10.5
MV-LV 6.5
36,100
20,000 110/121 ±8×1.25% 35 6.3 YNyn0d11 22.88 106.40 0.84 HV-MV 17.5–18.5
HV-LV 10.5
MV-LV 6.5
40,100
25,000 110/121 ±8×1.25% 35 6.3 YNyn0d11 27.04 126.35 0.78 HV-MV 17.5–18.5
HV-LV 10.5
MV-LV 6.5
45,500
31,500 110/121 ±8×1.25% 35 6.3 YNyn0d11 32.16 149.15 0.78 HV-MV 17.5–18.5
HV-LV 10.5
MV-LV 6.5
52,300
40,000 110/121 ±8×1.25% 35 6.3 YNyn0d11 38.56 179.55 0.73 HV-MV 17.5–18.5
HV-LV 10.5
MV-LV 6.5
64,900
50,000 110/121 ±8×1.25% 35 6.3 YNyn0d11 45.52 213.75 0.73 HV-MV 17.5–18.5
HV-LV 10.5
MV-LV 6.5
76,100
63,000 110/121 ±8×1.25% 35 6.3 YNyn0d11 54.16 256.50 0.67 HV-MV 17.5–18.5
HV-LV 10.5
MV-LV 6.5
86,500

*Three-winding SFS11 series (off-circuit) and SZS11 series (on-load) are also available. Please contact us for detailed specifications.*

110kV Two-Winding Power Transformer with Off-Circuit Tap-Changer

Rated Capacity (kVA) Voltage Combination Connection Symbol No-load loss(kW) No-load current(%) Full-load loss(kW) ShortCircuit Impedance (%)
High Voltage (kV) HV Tapping Range Low Voltage (kV)
6300 110
121
±2×2.5% 6.3
6.6
10.5
11
YNd11 9.3 0.6 36 10.5
8000 11.2 0.6 45
10000 13.2 0.55 53
12500 15.6 0.55 63
16000 18.8 0.5 77
20000 22 0.5 93
25000 26 0.45 110
31500 30.8 0.45 133
40000 36.8 0.4 156
50000 44 0.4 194
63000 52 0.35 234
75000 13.8
15.75
18
20
59 0.35 278 12-14
90000 68 0.3 320
120000 84.8 0.3 397
150000 100.2 0.3 472
180000 112.5 0.25 532

110kV Three-Winding Power Transformer with Off-Circuit Tap-Changer

Rated Capacity (kVA) Voltage Combination Connection Symbol No-load loss(kW) No-load current(%) Full-load loss(kW) ShortCircuit Impedance (%)
High Voltage (kV) HV Tapping Range Low Voltage (kV) step-down step-up
6300 110
121
±2×2.5%
35
37
38.5
±2×2.5% or ±5%
6.3
6.6
10.5
11
YNyn0d11 11.2 0.6 47 H-M
10.5H-L
17-18M-L
6.5
H-M
17-18H-L
10.5M-L
6.5
8000 13.3 0.6 56
10000 15.8 0.55 66
12500 18.4 0.55 78
16000 22.4 0.5 95
20000 26.4 0.5 112
25000 30.8 0.45 133
31500 36.8 0.45 157
40000 43.6 0.4 189
50000 52 0.4 225
63000 61.6 0.35 270

 

Ordering Information

To ensure accurate selection and timely delivery, please provide the following details when placing an order:

Product Model & Type (e.g., SFZ11, SFSZ11)

Rated Capacity (kVA)

Voltage Combinations (HV / MV / LV)

Tapping Range (e.g., ±2×2.5% or ±8×1.25%)

Number of Windings (two-winding or three-winding)

Tap Changer Type (off-circuit or on-load)

Connection Symbol (e.g., YNd11, YNyn0d11)

Frequency (50 Hz)

Optional Accessories (corrugated tank, special bushings, etc.)

 

Why Choose Our 110kV Oil-Immersed Transformers?

Low Loss & High Efficiency: Reduced no-load and load losses significantly lower operating costs over the transformer’s lifetime.

Low Noise & Low Partial Discharge: Optimized core clamping and advanced insulation design ensure quiet, reliable operation.

High Short-Circuit Strength: Robust winding support and lead structure withstand severe grid disturbances.

Maintenance-Free Design: Fully sealed construction prevents oil degradation and moisture ingress.

Versatile Configurations: Available in two-winding / three-winding, off-circuit / on-load tap changer, and multiple voltage combinations to meet diverse grid requirements.

Proven Reliability: Manufactured under strict quality control and tested to international standards.

Get in Touch with Liyond

We're here to help! Connect with our team for expert support and personalized solutions.

Power your projects with long-lasting switchgear and switchgear components from Liyond.

We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.          Privacy Policy
Reject Accept
error: Content is protected !!