VBI type vacuum circuit breaker conforms to national standard GB1984-2003 HV Vacuum Circuit Breaker, JB3855-1996<3.6-40.5kV indoor AC high voltage vacuum circuit breaker>, DL/T403-2000<12kv-40.5kv HV vacuum circuit breaker ordering technical conditions>, and IEC62271-100:2001 high voltage AC circuit breaker relevant regulations.
1. Ambient temperature is not greater than +40 ℃, not less than -10 ℃ (allow storage at -30 ℃);
2. Altitude below 1000m;
3. Daily average daily relative humidity of not more than 95%, the monthly average of not more than 90%; saturated vapor pressure daily average of not more than 2.2 * 10-3MPa, the monthly average of not less than 1.8 * 10-2MPa. When the temperature drops sharply, it may condense;
4. Earthquake intensity does not exceed 8;
5. No fire, explosion, serious pollution, chemical corrosion and severe vibration of the place.
| NO. | Name | Unit | data | ||
| * | Type | / | 口Insulating cylinder
口Epoxy resin embedded poles 口Nylon embedded poles
|
口Upper outlet
口Side outlet
|
|
| 1 | clearance between open contacts |
mm |
11±1 | ||
| 2 | overtravel | 3±0.5 | |||
| 3 | Interphase center distance | 210±1 | |||
| 4 | Contact closing bounce time |
ms |
≤2 | ||
| 5 | Three phase switching and switching out of synchronism | ≤2 | |||
| 6 | Opening time | ≤50 | |||
| 7 | Closing time | ≤100 | |||
| 8 | Average switching speed (6mm after contact separation) |
M/S |
0.9~1.3 | ||
| 9 | Average closing speed (6mm before contact closing) | 0.4~0.8 | |||
| 10 | Closing contact pressure | N | 25KA | 31.5KA | |
| 2200±200 | 3200±200 | ||||