FLN □ -24kV SF6 load break switch is a switch equipment for medium voltage switchgear, using SF6 gas as arc extinguishing and insulating medium. There are three working positions: open, closed, earth position in the switch.
Model meaning.: FL(R)N □ -24kV
The compact size, easy installation, and fine adaptability to environment make the switch suitable for many different applications.
It can be divided into two types: FLN □-24kV (K type single spring operating mechanism), FLRN □-24kV (A type double spring operating mechanism). The latter type could be equipped with fuse combination, having control and protecting function, which can be used for power supply and substation as a protecting and control device, especially suitable for ring main unit switchgear, cable distribution box and switching substation.
| MAIN TECHNICAL SPECIFICATION | UNIT | FLN □-24D/T630-20 Load break switch | FLRN □-24D/T100-31.5 LBS + Fuse-combination units | |||
| Rated voltage | kV | 24 | 24 | |||
| Rated frequency | Hz | 50 | 50 | |||
| Rated current | A | 630 | 100 | |||
| Short-duration (1min) power frequency withstand voltage | kV | 65 | 65 | |||
| Lightning impulse withstand voltage | kV | 125 | 125 | |||
| Rated power frequency withstand voltage(5min) | kV | 24 | 24 | |||
| Rated short-time withstand current (Load break switch/3s) | kA | 20 | 20 | |||
| Rated short-time withstand current(Earthing switch/2s) | kA | 20 | 20 | |||
| Rated peak withstand current(Load break switch) | kA | 50 | 50 | |||
| Rated peak withstand current(Earthing switch) | kA | 50 | 50 | |||
| Rated short-circuit making current(Load break switch) | kA | 50 | 125 | |||
| Rated short-circuit making current(Earthing switch) | kA | 50 | 50 | |||
| Rated closed-loop dropout current | A | 630 | ||||
| Rated active load breaking current | A | 630 | ||||
| Rated cable-charging breaking current | A | 10 | 10 | |||
| Rated short-circuit breaking current | kA | 31.5 | ||||
| Rated transfer current | A | 1400 | ||||
| Fuse type | XRNT-12kV/100A | |||||
| Fuse impact output energy | J | 1±0.5 | ||||
| Mechanical endurance LBS/Earthing switch | Time | 3000/2000 | 3000 | |||
| Air insulation distance of charged body and ground | mm | ≥ 180 | ≥ 180 | |||
| SF6 Gas pressure(Relative pressure at 20℃ ) | bar | 0.4 | 0.4 | |||
| Opening and Closing simultaneity | ms | ≤ 2 | ≤ 2 | |||
1. Ambient temperature:-40℃ ~+40℃
2. Relative humidity: daily average ≤ 95%, monthly average ≤ 90%
3. Altitude: ≤ 2000m
4. Earthquake intensity:≤ 8 degree
5. No corrosive gas, no combustible gas, no steam and shake.
*Annual leakage rate ≤ 0.1%
*Special conditions:When the altitude > 2000m,please indicate in order to adjust the designing scheme.
K type spring dual-function operating mechanism
As an inlet control unit for FLN□-24kV, the working principle of K type spring operating mechanism is spring press and release.
Earthing operation
Driven by the handle, upper crank arm rotates and presses spring 2 to store energy, when the max energy reaches continue rotate the rank arm, the energy storage spring starts to release energy and drive the upper trigger, enables the connecting bar to drive the crank arm, crank arm rotates and drives the moving contactor for earthing.
Switch on operation
Driven by the handle, lower crank arm 1 rotates, presses spring 2 to store energy, when the energy released, it drives the trigger 8, enables connecting bar to drive the crank arm, crank arm rotates and drives the moving contactor and LBS load break switch turns on.
Switch off operation
Rotate the main shaft crank arm counterclockwise by the handle, release the energy storage spring and the load break switch turns off.
A type spring dual-function operating mechanism
As a outlet control unit for FLRN□-24kV.
Working principle of A type mechanism is same as K type, in addition, it has fuse striker trip function. For A type mechanism. Electromagnetic trip is also available for customers requirement.
Switch on operation
Driven by the handle, lower crank arm 1 rotates to press switch on spring 12 and switch off spring 8 at the same time, to provide sufficient energy required by switching off. When the lower crank arm 1 buckles the pin and drives trigger to move, it makes the lower roller wheel tripped, and release the switch on spring and load break switch turns on.
Switch off operation
Press the switch off button or push the trip pin 2 by the fuse striker, release the spring and load switch turns off.
Earth operation
Earthing operation of A type mechanism is the same as that of K type.
Motor operation can be added to both types of operating mechanisms, which means it can be operated manually or motorized.
Operating voltage: DC48V AC/DC 110V 220V