Cast Resin Dry Type Transformer Manufacturer, SCB10 35kV Dry Type Transformer | Liyond
Home/Power Transformer/Dry-Type Transformer/35kV Cast Resin Dry-Type Transformer SCB10 Series up to 6300kVA

35kV Cast Resin Dry-Type Transformer SCB10 Series up to 6300kVA

The SC(B)10 series epoxy resin cast dry-type transformer is designed for indoor applications where fire safety, environmental cleanliness, and minimal maintenance are critical. With a 35kV voltage class, this transformer is ideal for use in high-rise buildings, hospitals, shopping centers, schools, underground substations, power plants, oil fields, and mining operations. It fully complies with GB1094.1-5 and GB1094.11 standards, ensuring reliable performance in demanding environments.

Electrical ProductsElectrical Products

Key Structural Features of 35kV Epoxy Resin Cast Dry-Type Transformer

Fire Safety & Environmental Protection
Epoxy resin cast construction ensures self-extinguishing properties, making the transformer safe for installation in fire-sensitive areas. No risk of oil leakage, fully environmentally friendly.

Low Loss & High Efficiency
Optimized core and winding design results in low no-load and load losses, reducing operational costs over the transformer’s lifetime.

Low Noise Level
Special core structure and resin encapsulation significantly reduce operational noise, suitable for noise-sensitive environments.

High Reliability
Thousands of units in service demonstrate performance reaching international reliability standards.

Excellent Moisture Resistance
Can operate normally in 100% humidity conditions. Requires no pre-drying before restarting after shutdown.

Maintenance-Free
No oil or cooling medium required. Minimal maintenance reduces total cost of ownership.

Structural Characteristics

Core
High-permeability grain-oriented cold-rolled silicon steel.

45° full miter multi-step core joints.

Square tube pull-rod structure with core column bound by insulating tape.

Special resin coating on core surface prevents rust and moisture ingress.

Effectively reduces no-load loss, excitation current, and noise.

Windings (Foil-Wound Low Voltage Coils)
Low voltage windings use full-section copper foil with Class F insulation.

Wound on dedicated foil winding machines for uniform ampere-turn distribution.

Eliminates issues such as high short-circuit stress, poor heat dissipation, and welding inconsistencies found in traditional wire-wound coils.

Coil ends are resin-sealed and cured for enhanced moisture and contamination protection.

Temperature Control System
Equipped with BWDK series digital temperature controller.

Temperature sensors embedded in the upper part of each low voltage coil.

Provides automatic three-phase temperature monitoring, display, over-temperature alarm, and trip functions.

Main Technical Parameters

Rated Capacity (kVA) Voltage Combination Connection Symbol Loss (kW) No‑Load Current (%) Short‑Circuit Impedance (%) Weight (Unit Only) (kg) Weight (With Enclosure) (kg)
High Voltage (kV) HV Tapping Range Low Voltage (kV) Losses (Load 120℃) Losses (No-load)
50 38.5
35
±5%
±2×2.5%
0.4 Yyn0
Dyn11
1.43 0.45 2.80 6 720 770
100 2.09 0.63 2.4 890 950
160 2.83 0.792 1.8 1000 1060
200 3.33 0.88 1.8 1260 1320
250 3.8 0.99 1.60 1420 1480
315 4.51 1.18 1.6 1730 1790
400 5.42 1.38 1.4 1840 1900
500 6.65 1.62 1.4 2200 2270
630 7.7 1.86 1.2 2630 2700
800 9,12 2.16 1.2 3260 3330
1000 10.45 2.43 1 3990 4060
1250 12.73 2.84 0.9 4470 4540
1600 15.49 3.24 0.9 5570 5640
2000 18.24 3.83 0.9 6410 6480
2500 21.85 4.46 0.9 6930 7030

Outline and Mounting Dimensions

SC(B)10 Series 35kV Epoxy Resin Cast Dry-Type Transformer drawing

Rated Capacity (kVA) Outline and Mounting Dimensions (mm)
L W H C1 C2
50 1180 890 1050 660 660
100 1250 900 1350 660 660
160 1540 920 1660 820 820
200 1620 920 1750 820 820
250 1650 940 1800 820 820
315 1670 940 1850 820 820
400 1720 1150 1900 820 820
500 1810 1150 1940 820 1070
630 1850 1150 1990 820 1070
800 1990 1150 2010 820 1070
1000 2020 1150 2040 1070 1070
1250 2080 1150 2120 1070 1070
1600 2130 1150 2320 1070 1070
2000 2180 1150 2480 1070 1070
2500 2200 1150 2600 1070 1070
3150 2580 1320 2610 1070 1070
4000 2680 1320 2650 1070 1070
5000 2890 1350 2680 1475 1070
6300 2980 1700 2800 1475 1070

Ordering Information

To ensure accurate selection and timely delivery, please provide the following details when placing an order:

Product Model

Rated Capacity (kVA)

High Voltage / Low Voltage Ratings (kV)

High Voltage Tapping Range

Number of Phases (typically 3-phase)

Frequency (50 Hz)

Connection Symbol (Yyn0 or Dyn11)

Enclosure Requirements (if applicable)

 

Why Choose This Transformer?

Safe for Indoor Use: Fire-resistant, non-toxic, and self-extinguishing.

Energy Efficient: Low losses contribute to lower operating costs.

Environmentally Friendly: No oil, no risk of leakage or contamination.

Proven Reliability: Designed and tested to meet rigorous international standards.

Easy Installation: Compact footprint, suitable for direct installation at load centers.

 

Get in Touch with Liyond

We're here to help! Connect with our team for expert support and personalized solutions.

Related Dry-Type Transformer

Check out these related products you might also be interested in.

Get A Quote

Power your projects with long-lasting switchgear and switchgear components from Liyond.

We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.          Privacy Policy
Reject Accept
error: Content is protected !!