logo

FN18 High Voltage Load Break Switch Nalf Air Insulation Switch Breakers Fuse Switch

FN18 load switch

 

  • FN18 High Voltage Load Break Switch Nalf Air Insulation Switch Breakers Fuse Switch

    FN18-口is a general purpose, three-pole, load break switch that offers switchgear owners and assemblers the advantages of an advanced interrupting technology and proven, dependable performance in a compact design. The switch is available to switchgear assemblers as a building block for metal-enclosed and pad-mounted switchgear applications in ratings from 12-40.5 kV.
    The standard FN18 switch includes a heavy-duty steel frame with stand-off insulators, a unique puffer-type arc extinguishing system, an operating mechanism and current-carrying components, including blade-type interrupters with cast hinges and jaw connectors.
    Optional accessories and features include a variety of operating handles, a motor operator, auxiliary switches, a shunt trip device, fuse bases, mechanical fuse tripping, grounding switches, mechanical door interlocking and key interlocking.

    FN18 series indoor high-voltage load switch has the advantages of easy design, operation, compact structure, small volume, full function, light weight, fast breaking and closing speed and high reliability. It is suitable for AC 50Hz, rated voltage 12kV, 24kV, rated current 630A and three-phase distribution system, especially for city network construction and renovation projects, high-rise buildings, ring network power supply of public facilities, and is an ideal product for box-type substation and transformer protection.

  • FN18 High Voltage Load Break Switch Nalf Air Insulation Switch Breakers Fuse Switch
    Rated voltage Unit 12kV 17.5kV 24kV 36kV 40.5kV
    Rated current A 400 630 1250 400 630 1250 400 630 1250 630 800 1000 630 800 1000
    Max.rated current A 400 630 1250 400 630 1250 400 630 1250 630 800 800 630 800 800
    Short circuit making capacity KA peak 67 50 50 50 50
    Peak withstand current* KA peak 82 82 82 66 66
    Short time current 1 sec. KA eff 31.5

    25

    20

    31.5

    25

    20

    31.5

    25

    20

    31.5

    25

    31.5

    25

    31.5

    25

    25

    25

    16

    25

    25

    16

    31.5

    25 

    16

    25 25 25 25 25 25
    2 sec.
    3 sec.
    Mainly active load breaking capacity

    (test duty 1 and, IEC 60265-1( 265))

    A 400 630 1250 400 630 1250 400 630 1250 630 800 630 800 630 800
    Mainly capacitive breaking capacity

    (test duty 4, IEC 60265-1 (IEC 265))

    A 150 45 80 50 50
    Mainly inductive breakingcapacity cosφ=0.15 A 16 16 16 16 16
    Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11) A 1600 1600   1600 1600   900 900   300* 300 300 300 300 300
    Power frequency withstand voltage 50 Hz 1 min.  

    -to earth and between poles                                 

    -across isolating distance

    kV 42

    45

    45

    60

    55 

    70

    80

    88

    95

    120

    Impulse withstand voltage 1.2/50 μs

     – to earth and between poles   

    – across isolating distance

    kV

    75

    85

    95

    110

    125

    145

    170

    195

    190

    220

    Pole distance mm 150, 170, 210 170,210 170,235,275 360 360
    Max. operating torque at:

    -closing K/A mech.                                           

    -opening K/A mech.

    Nm 115-120 Nm
    K-mech.120 Nm/A-mech. 3Nm
    80-100 Nm
    K-mech.80-100 Nm
    Operating angle on the shaft degree 130 120
    Opening time ms 40-60 60
    FN18 Outline Dimension Drawing

    FN18 load break switch drawing

    FN18 load break switch drawing

    FN18 load break switch structure

    FN18 lbs structure

FN18 High Voltage Load Break Switch Nalf Air Insulation Switch Breakers Fuse Switch