DSN-DM/Z DSN-DM/Y Indoor Electromagnetic lock
-
DSN-DM/Z DSN-DM/Y Indoor Electromagnetic lock
DSN-DM type indoor electromagnetic lock is used for 3.6 ~ 40.5 KV rated voltage and frequency of 50 hz indoor high voltage electrical equipment. With pillar type voltage sensor, used to run personnel provide information on the condition of the circuit voltage switch equipment installation place and function of subject to compulsory atresia, assembly before all kinds of switch cabinet, the back door and other parts need to be blocking, prevent electrical wrong operation, prevent into charged interval, improve the product of form a complete set of error prevention performance.
Warning: only by the display of charged display device was not enough to prove the system has not been charged; Like to run the program as a mandatory requirements, should also be used in accordance with the relevant IEC 61243 voltage detector or voltage detection device.
Using the environment conditions
1.Ambient temperature: the upper limit of no more than +40℃, the lower limit of not less than -25℃, a special area of not less than -35℃
2.Altitude: not more than 1000m above sea level Area
3.Atmospheric conditions: air relative humidity on average less than 95%, on average less than 90%; daily average water vapor pressure less than 2.2kPa, on average less than 1.8kPa
4.Environmental conditions: no significant contamination, non-flammable, explosive chemicals and salt spray spaces
Product features
☆Unlock the direction and lock in the same direction, unlock keys can be used to after the unlock, continue to spin can directly open the lock, convenient operation.
Execution standard:JB/T7827-95
IEC 61958:2000 DL/T538
-
Installation hole size shape
Models and meaning
Back view the wiring diagram
Note: the so-called installed the left or right, refers to the operator to lock objects (such as lever, cabinet put oneself in another’s position fixed part), the corresponding installation position. When electromagnetic locks in the lock on the object location, is located in the operator to the left side is the left side of the installation, on the other hand, is on the right side of the installation.
Electromagnetic lock is chosen, and basic parameters
Order
No.Model Electromagnetic lock according to
the luminous componentElectromagnetic lock
operating
voltage (V)Installation Dimensions
and
installation
hole
size chartBack
asthe
wiring
diagramRemark Type operating
voltage (V)Effective
life (h)D-13 DSN-DMY1 Ultra-high brightnesslight-emitting tube <DC2.5 >30000 AC220DC220 Right open Figure 1 Figure 3 D-14 DSN-DMY3 DC110 Right open Figure 1 D-15 DSN-DMY4 AC110 Right open Figure 2 D-16 DSN-DMZ1 AC220DC220 Left open Figure 2 D-17 DSN-DMZ3 DC110 Left open Figure 2 D-18 DSN-DMZ4 AC110 Left open Figure 1 D-19 DSN-DMY6 DC6 Right open Figure 2 Designed
with
uninterruptible
power supply.D-20 DSN-DMZ6 DC6 Left open Figure 2 Ordering instructions
1. To order this product, please indicate the type, voltage sensor model, please refer to our company sample voltage sensor.
2. If you have special requirements can be negotiated with our company.
If you would like a quotation or further information on this product, please fill in the form below and we will reply to you within 1 working day.