VSG-C/12 Series Indoor High Voltage Lateral Type Vacuum Circuit Breaker With VSG Operating Mechanism
-
VSG-C/12 Series Indoor High Voltage Lateral Type Vacuum Circuit Breaker With VSG Operating Mechanism
General Description:
VSG-C/12 lateral type indoor high voltage vacuum circuit breaker used spring to storage energy. The operating mechanism can be operated by two ways, by manual and electromotive operation, The characteristics is according with GB1984-2003 High Voltage AC Circuit Breaker, JB3855-1996 3.6-4.5KV Indoor AC High Voltage AC Circuit Breaker and IEC standard 62271-100:200162271-100:2001 High Voltage AC Circuit Breaker
Applying Ambient Conditions:
1. Ambient temperature: -25℃一+40℃
2. Relative humidity: the average humidity of a day should be no mare than 95%; the average humidity of a month should be no more than 90 %.
3. Saturated vapor pressure: the average pressure of a day should be no more than 2. 2kPa, the average humidity of a month should be no more than 1.8kPa.
4. Earthquake intensity: not exceed 8 degrees.
5. Height above sea level: ≤1000m(not including special requirements)
6. Environmental conditions: It should be used in the places without fire, explosion, serious filth, chemical erosion and violent VSL ration. -
Main technical parameters:
NO. Item Unit Data Type / Insulating cylinder/ Epoxy resin embedded poles/ Nylon embedded poles Upper outlet/ Right outlet
1 Rated voltage KV 12 2 Rated short time power frequency withstand voltage(1min) 42 3 Rated lighting impluse withstand voltage(peak) 75 4 Rate frequency Hz 50 5 Rated current A 630,1250 630,1250 6 Rated short-circuit breaking current KA 25 31.5 7 Rated short time withstand current 25 31.5 8 Rated short-circuit duration s 4 9 Rated peak withstand current KA 63 80 10 Rated short-circuit closing current 63 80 11 Power frequency withstand voltage of secondary circuit(1 min) v 2000 12 Rated single/ back-to-back capacitor bank breaking current A 630/400 13 Switching time ms 20-50 14 Closing time 35-70 15 Mechanical life time M2 level 10000(630-125/25-31.5) 16 Electrical life E2 level 17 Moving and fixed contacts allow wear accumulation thickness mm 3 18 Rated closing operating voltage v AC110/AC220/DC110/DC220 19 Rate breaking operating voltage 20 Rated voltage of energy starge motor 21 Rate power of energy storage motor w 90 22 Storage time s ≤15 23 Contact distance mm 11±1 24 Over stroke 3±1 25 Rated order of operation / O-0.3s-CO-180s-CO VSG-C/12 Side mounted vacuum circuit breaker dimensions reference